Chapter 9. Diagnostics
GFK-2950C February 2018 425
9.5.3 I/O Fault Categories
Category
Fault Type
Fault Description
Fault Extra Data
Circuit Fault (1)
Discrete Fault (1)
Loss of User Side Power
(01 hex)
Circuit Configuration
Short Circuit in User Wiring
(02 hex)
Circuit Configuration
Sustained Overcurrent
(04 hex)
Circuit Configuration
Low or No Current Flow
(08 hex)
Circuit Configuration
Switch Temperature Too
High (10 hex)
Circuit Configuration
Switch Failure (20 hex)
Circuit Configuration
Point Fault (83 hex)
Circuit Configuration
Output Fuse Blown (84 hex)
Circuit Configuration
Analog Fault (2)
Input Channel Low Alarm
(01 hex)
Circuit Configuration
Input Channel High Alarm
(02 hex)
Circuit Configuration
Input Channel Under Range
(04 hex)
Circuit Configuration
Input Channel Over Range
(08 hex)
Circuit Configuration
Input Channel Open Wire
(10 hex)
Circuit Configuration
Over Range or Open Wire
(18 hex)
Circuit Configuration
Output Channel Under Range
(20 hex)
Circuit Configuration
Output Channel Over Range
(40 hex)
Circuit Configuration
Expansion Channel Not
Responding
(80 hex)
Circuit Configuration
Invalid Data (81 hex)