Chapter 6. Service Request Function
GFK-2950C February 2018 311
6.21.1 Non-Extended Formats
Input Parameter Block Format
Amount of Retuned Data
Address + 0
00h = Read Controller Fault Table
01h = Read I/O Fault Table
41h = Read I/O Fault Table with Remote Fault Record
693 registers required for resulting output
693 registers required for resulting output
757 registers required for resulting output
Address + 1
Always 0
Non-Extended Output Parameter Block Format
Controller Fault Table Output Format
Address
I/O Fault Table Output Format
High Byte
Low Byte
High Byte
Low Byte
Unused
00h = Controller Fault Table
Address+0
Unused
01h = I/O Fault Table
Unused
Always zero (0)
Address+1
Unused
Always zero (0)
Unused
Unused
Address+2
Unused
Unused
Unused
Unused
Address+3
Address+14
Unused
Unused
Minutes
Seconds
Address+15
Address+17
(Time Since Last Clear,
in BCD Format)
Minutes
Seconds
Day of Month
Hour
Day of month
Hour
Year
Month
Year
Month
Number of faults since last clear
Address+18
Number of faults since last clear
Number of faults in queue
Address+19
Number of faults in queue
Number of faults read
Address+20
Number of faults read
Start of fault data
Address+21
Start of fault data
Address
I/O Fault Table Output Format
High Byte
Low Byte
Address+0
Unused
41h = I/O Fault Table
with Remote Fault
Record
Address+1
Starting index of faults to be read
Address+2
Number of faults to be read
Address+3
Address+14
Unused
Unused
Address+15
Address+17
(Time Since Last Clear,
in BCD Format)
Minutes
Seconds
Day of month
Hour
Year
Month
Address+18
Number of faults since last clear
Address+19
Number of faults in queue
Address+20
Number of faults read
Address+21
Start of fault data