EasyManua.ls Logo

GE PACSystems RX7i

GE PACSystems RX7i
469 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 3. Program Data
60 PACSystems* RX7i, RX3i and RSTi-EP CPU Programmer's Reference Manual GFK-2950C
3.12 Word-for-Word Changes
Many changes to the program that do not modify the size of the program are considered word-for-
word changes. Examples include changing the type of contact or coil, or changing a reference
address used for an existing function block.
The following are word-for-word changes:
Switching between two symbolic variables
Switching between a symbolic variable and a mapped variable
Switching between a constant and a symbolic variable
3.12.1 Exception: Symbolic Variables
Creating, deleting, or modifying a symbolic variable definition is not a word-for-word change.

Table of Contents

Other manuals for GE PACSystems RX7i

Related product manuals