Chapter 9. Diagnostics
GFK-2950C February 2018 409
9.4.9 Module Hardware Failure (Group 14)
The fault group Module Hardware Failure occurs when the CPU detects a non-fatal hardware failure
on any module in the system, for example, a serial port failure on a LAN interface module. The fault
action for this group is Diagnostic.
Action: Non-configurable.
1A0 hex/416 decimal, Missing 12 Volt Power Supply
A power supply that supplies 12 volts is required to operate the LAN Interface module.
Correction
1) Install/replace a 100 watt power supply.
2) Connect an external VME power supply that supplies 12 volts.
1C2 - 1C6 hex (450 454 decimal), LAN Interface Hardware Failure
Refer to the LAN Interface manual, GFK-0868 or GFK-0869 (previously GFK-0533), for a description
of these errors.
All Others, Module Hardware Failure
A module hardware failure has been detected.
Correction
Replace the affected module.