Chapter 6. Service Request Function
312 PACSystems* RX7i, RX3i and RSTi-EP CPU Programmer's Reference Manual GFK-2950C
For the non-extended formats, the returned data for each fault consists of 21 words (42 bytes) for
00h and 01h and 23 words (46 bytes) for 41h. This request returns 16 Controller Fault Table entries
or 32 I/O Fault Table entries, or the actual number of faults, if fewer. If the fault table read is empty,
no data is returned.
The following tables show the return format of a Controller Fault Table entry and an I/O Fault Table
entry.
Format of Returned Data for Fault Table Entries
Format for Parameter Setting 00h or 01h
Controller Fault Table (00h) Output Format
Address
I/O Fault Table (01h) Output Format
High Byte
Low Byte
High Byte
Low Byte
Unused
Long/short
Address+21
Memory type
Long/Short
7
Unused
Unused
Address+22
Offset
Slot
Rack
Address+23
Slot
Rack
Task
Address+24
Bus address
I/O Bus Number (block)
Fault action
Fault group
Address+25
Point
Error code
Address+26
Fault action
Fault group
Fault extra data
Address+27
Fault type
Fault category
Address+28
Fault extra data
Fault description
Address+29
Address+38
Fault extra data
Minutes
Seconds
Address+39
Address+41
(Time-stamp,
in BCD Format)
Minutes
Seconds
Day of month
Hour
Day of month
Hour
Year
Month
Year
Month
Start of next fault output parameter block
Address+42
Start of next fault output parameter block
7
The Long/Short indicator in the low byte of
Address + 21
specifies the amount of fault data present in the fault entry:
Fault Table
Long/Short Value
Fault Data Returned
Controller
00
8 bytes of fault extra data present in the fault entry
01
24 bytes of fault extra data
I/O
02
5 bytes of fault extra data
03
21 bytes of fault extra data