Fault References for Non-Configurable Faults
CPU hardware fault (such as failed
memory device or failed serial port).
Sets #SY_FLT, #SY_PRES, #HRD_FLT
Non-fatal hardware fault on any module in
the system, such as failure of a serial port
on a LAN interface module.
Sets #SY_FLT, #SY_PRES, #HRD_FLT
A diagnostic PROFINET alarm has been
received and an I/O fault has been logged
in group 28.
Sets #ANY_FLT, #IO_FLT, #IO_PRES
Non-recoverable software error in a LAN
interface module.
Sets #SY_FLT, #SY_PRES, #SFT_FLT
Program or block checksum failure during
power-up or in RUN Mode.
The low battery indication is not
supported for all CPU versions. For details,
refer to Battery Status (Group 18).
Constant sweep time exceeded.
#SY_FULL
#IO_FULL
(diagnostic)
Controller fault table full (64 entries).
I/O Fault Table full (64 entries).
Sets #SY_FLT, #SY_PRES, #IO_FLT,
#IO_PRES
New rack added, extra rack, or previously
faulted rack has returned.
Extra IOC, previously faulted I/O Controller
is no longer faulted.
Extra IO module, or previously faulted I/O
module is no longer faulted.
New intelligent module is added, or
previously faulted module no longer
faulted.
Point or channel on an I/O module; a
partial failure of the module.
No application program is present at
power-up. Should only occur the first time
the PACSystems controller is powered up
or if the user memory containing the
program fails.
CPU will not go to RUN Mode; it
continues executing STOP Mode
sweep until a valid program is loaded.
This can be a null program that does
nothing. Sets #SY_FLT and #SY_PRES.
Corrupted program memory at power-up.
Program could not be read and/or did not
pass checksum tests.
Sets #SY_FLT and #SY_PRES.