4.15. Submenu PID.GR - Configuring groups of control parameters
Acronym Scrolling message Password Description
PID.GR PID GROUP
PARAMETERS CONFIG
Level 1 Lets you configure groups of control parameters. Groups of
control parameters must be enabled with the parameter PID.
GN = .1...4 on the MODE menu (the menu is not shown if PID.
GN = 0).
Groups are used to preconfigure sets of function parameters
that can be easily called when needed, without having to re-
configure the PID parameters every time. The number of pa-
rameters available in groups is less than the number on the
PID submenu. The number of parameters available in groups
is limited to those for PID heating and/or cooling control.
PID.N
PID.G.N
H.PB
H.IT
H.DT
H.P.HI
H.P.LO
C.PB
C.IT
C.DT
C.P.HI
C.P.LO
PV.THR
Selecting the parameter
group to be configured
123
Minimum limit of
cooling power
125
Selecting the parameter
group to be configured
123
Threshold PV for the
activation of the group
of PID parameters
125
Proportional heating
band or hysteresis in
ON-OFF control
123
Integral heating time 123
Derivative heating time 123
Maximum limit of
heating power
74
Minimum limit of
heating power
124
Proportional cooling
band or hysteresis in
ON-OFF control
124
Integral cooling time 124
Derivative cooling time 124
Maximum limit of
cooling power
<?>
Parameter Pag. Parameter Pag.