80209C_MHW_850-1650-1850_02-2020_ENG_pag. 176
4.28.5. DS.SP - Selecting the SV display
Acronym Scrolling message Submenu Attributes
dS.SP HOME.1 (o HOME.2) SV DISPLAY FUNCTION HOME R W
The parameter shows and sets the display assigned to the SV display.
Unit of measurement: -
Options: NONE = None (display off)
SETP = Local setpoint / manual power or active setpoint (read only), in case of enabling Multiset
function, setpoint gradient, remote setpoint, and programmer (if enabled).
SSP = Active setpoint (read only)
if the model with auxiliary input
IN2 = Auxiliary input
OUT.P = Power control output (on 1850 LED % on)
SP-PV = Deviation |SP-PV|
HEAT = Heating power output with 0...100% control (on 1850 LED % on)
COOL = Cooling power output with 0...100% control (on 1850 LED % on)
HE+CO = Power control output -100...100% (positive for heating, negative for cooling)
(on 1850 LED % on)
if the model with CT1+CT2:
CURR1 = Current input CT1 (on 1850 LED A on)
CURR2 = Current input CT2 (on 1850 LED A on)
if ENERG function enabled and model with CT1+CT2:
CURR = Load current (on 1850 LED A on)
if the ENERG function is enabled
OUT.KW = Power on load (on 1850 LED KW on)
EN.KWH = Energy transferred to load ((on 1850 LED KWh on)
if the Timer function is enabled:
TIM.RE = Remaining timer value
TIM.EL = Timer value lapsed
if controller model with valve control:
V.POSI = Valve position (on 1850 LED % on)
if the Programmer function is enabled in parameter PROGR on the EN.FUN menu:
P.TIME = Current step time (ramp or hold)
P.T.TIM = Program total theoretical time (only for model 850)
P.E.TIM = Program total real time (only for model 850)
P.R.TIM = Program total theoretical residual time (only for model 850)
IN1 = Main input
if model with auxiliar input 2
IN3 = Auxiliar input 2
if model with Modbus Master serial and Master parameter configured:
MAS.01 = Master value 1
MAS.02 = Master value 2
MAS.03 = Master value 3
MAS.04 = Master value 4
MAS.05 = Master value 5
MAS.06 = Master value 6
MAS.07 = Master value 7
MAS.08 = Master value 8
MAS.09 = Master value 9