80209C_MHW_850-1650-1850_02-2020_ENG_pag. 58
4.4.1. SW.VER - Software version
Acronym Scrolling message Submenu Attributes
SW.VER SOFTWARE VERSION INFO R
The parameter shows the version (major.minor) of the controller software.
Unit of measurement: -
Options: -
4.4.2. CODE - Identifying code of controller
Acronym Scrolling message Submenu Attributes
CODE INSTRUMENT ID CODE FOR SERIAL COMM INFO R
The parameter shows identifying code of the device for serial communication.
Unit of measurement: -
Options: 0...247
4.4.3. ERR.1 - Main input error
Acronym Scrolling message Submenu Attributes
ERR.1 INPUT ERROR INFO R
The parameter shows error detected by the main input.
Unit of measurement: -
Options: Lou = Value below minimum scale limit
HIGH = Value above maximum scale limit
Err = PT100 in short circuit or value below minimum limit
(for example TC with wrong connection)
Sbr = Sensor break or value above maximum limit
ECAL = Calibration error
EAdC = AD converter error
4.4.4. ERR.2 - Auxiliary input error
Acronym Scrolling message Submenu Attributes
ERR.2 INPUT ERROR INFO R
The parameter displays the error (if present) detected on the optional auxiliary input (if available).
Unit of measurement: -
Options: Lou = Value below minimum scale limit
HIGH = Value above maximum scale limit
Err = PT100 in short circuit or value below minimum limit
(for example TC with wrong connection)
Sbr = Sensor break or value above maximum limit
ECAL = Calibration error
EAdC = AD converter error