EasyManua.ls Logo

gefran SIEIDrive ADV100 - Analog Output Configuration

gefran SIEIDrive ADV100
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
58 ADV100 • Quick installation guide - Specifications and connection
Step 1 - Electrical connections
Make the connections as described in paragraph 7.4.2.
Checks to be performed before powering the drive
Check that the supply voltage is correct and that the input terminals on the drive (L1, L2 and L3) are connected
correctly.
Check that the output terminals on the drive (U, V and W) are connected to the motor correctly.
Check that all the drive control circuit terminals are connected correctly. Check that all control inputs are open.
Powering the drive
After completing all the checks described above, power the drive and proceed to step 2.
Step 2 - Setting motor parameters
Set the rating data of the motor connected: rated voltage, rated frequency, rated current, rated speed, rated power,
power factor (cosφ).
10 Hp
Motor: 3 phase
720 rpm
Motor & Co.
Type: ABCDE
380 V
IP54
Made in ..............
19.0 A
IEC 34-1 / VDE 0530
Iso Kl F
Nr
.
12345-91
S1
50 Hz
Power factor
0.83
I nom
Rated voltage
Rated power
Rated speed (n )
N
The self-tuning procedure is described below using the data of an imaginary motor by way of example.
STARTUP WIZARD
Set motor data?
E=Yes Down=Next
E
SEQ
SEQ. 01 PAR: 2000
Rated voltage
400 V
Def: 400
E
SEQ
SEQ. 01 PAR: 2000
Rated voltage
000000400 v
Def: 400
401 v
399 v
E
SEQ
SEQ. 02 PAR: 2002
Rated current
11.8 A
Def: 11.8
E
SEQ
SEQ. 02 PAR: 2002
Rated current
00000011.8 A
Def: 11.8
11.9 A
11.7 A
E
SEQ
SEQ. 03 PAR: 2004
Rated speed
1450 r
p
m
Def: 1450
E
SEQ
SEQ. 03 PAR: 2004
Rated speed
0000001450 r
p
m
Def: 1450
1451 rpm
1449 rpm
E
SEQ
SEQ. 04 PAR: 2006
Rated frequency
50 Hz
Def: 50
E
SEQ
SEQ. 04 PAR: 2006
Rated frequency
000000050 Hz
Def: 50
51 Hz
49 Hz
E
SEQ
SEQ. 05 PAR: 2008
Pole pairs
2
Def: 2
E
SEQ
SEQ. 05 PAR: 2008
Pole pairs
2
Def: 2
3
1
E
SEQ
SEQ. 06 PAR: 2010
Rated power
5.50 kW
Def: 5.50
E
SEQ
SEQ. 06 PAR: 2010
Rated power
0000005.50 kW
Def: 5.50
5.51 kW
5.49 kW
E
SEQ
SEQ. 07 PAR: 2012
Rated power factor
0.83
Def: 0.83
E
SEQ
SEQ. 07 PAR: 2012
Rated power factor
0.83
Def: 0.83
0.84
0.82
E
Set the plate data of the motor connected, according to the procedures described on the previous pages.
Rated voltage [V]: the rated voltage of the motor indicated on the data plate.
Rated current [A]: motor rated current; approximately, the value should not be less than 0.3 times the rated current of the drive, output current class 1 @ 400 V
on the data plate of the drive.

Table of Contents