198
*1: If the regeneration power has only occurred during the interval, P_DEM = 0 and
PF_DEM = 1.
Integrated
power
Total integrated power from the start of time-series measurement
WP+_INTEG[Wh]_1 to WP+_INTEG[Wh]_4 Integrated active power
(consumption), Circuit 1-4
Wh
WP-_INTEG[Wh]_1 to WP-_INTEG[Wh]_4 Integrated active power
(regeneration), Circuit 1-4
Wh
WQ+_INTEG[varh]_1 to WQ+_INTEG[varh]_4 Integrated reactive power (lag),
Circuit 1-4
varh
WQ-_INTEG[varh]_1 to WQ-_INTEG[varh]_4 Integrated reactive power
(lead), Circuit 1-4
varh
Demand Integrated power within interval
WP+_INTVL[Wh]_1 to WP+_INTVL[Wh]_4 Integrated active power
(consumption), Circuit 1-4
Wh
WP-_INTVL[Wh]_1 to WP-_INTVL[Wh]_4 Integrated active power
(regeneration), Circuit 1-4
Wh
WQ+_INTVL[varh]_1 to WQ+_INTVL[varh]_4 Integrated reactive power (lag),
Circuit 1-4
varh
WQ-_INTVL[varh]_1 to WQ-_INTVL[varh]_4 Integrated reactive power
(lead), Circuit 1-4
varh
Average value within interval (demand value)
P_DEM[W]_1 to P_DEM[W]_4 Average value within time
Active power (Consumption),
Circuit 1-4
W
Q_DEM[var]_1 to Q_DEM[var]_4 Average value within time
Reactive power (LAG),
Circuit 1-4
var
PF_DEM_1 to PF_DEM_4 Average value within time
Power factor, Circuit 1-4
Maximum demand value during time-series measurement
P_DEM_MAX[W]_1 to P_DEM_MAX[W]_4 Maximum demand value,
Active power,
, Circuit 1-4
W
P_DEM_MAX DATE_1 to P_DEM_MAX DATE_4 Date of occurrence of maxi-
mum demand yyyy/m/d
, Circuit 1-4
P_DEM_MAX TIME_1 to P_DEM_MAX TIME_4 Time of occurrence of maxi-
mum demand
h:mm:ss, Circuit 1-4
Classification Data Header Contents Unit
P_DEM
P_DEM
2
+Q_DEM
2
*1
• "INST" in the header will be replaced by "AVE" for the average-
value data.
• "INST" in the header will be replaced by "MAX" for the maxi-
mum-value data.
• "INST" in the header will be replaced by "MIN" for the mini-
mum-value data.