4.2 Connection Methods
49
1
2
3
4
5
6
7
8
9
10
11
4.2.5 Checking the Wiring
Check to see if the 3169-20/21 is correctly connected to the line to
be measured.
The wiring check function may indicate incorrect connection
even when the actual connection is correct, or vice versa.
Check the vectors and measurements as well.
The length of a vector is not related to input level. It only indi-
cates the phase relationship.
A minus sign (-) with the phase angle indicates a lag phase
angle; a plus sign (+) indicates a lead phase angle. The phase
angle is calculated using the phase of the fundamental of the
PLL source (U
1
) as a reference.
The voltage levels, current levels, and phase angles displayed
on-screen are those of the fundamental component.
Press the
MEASURE
key to display the measurement screen.
Press the
F1
(SCREEN) key to display the selection window.
Select "WIRING CHECK" by using the cursor key.
Press the F1 (select) key; the wiring check will appear.
The connection status is shown by the voltage, current vectors,
and the connection check result.
SCREEN
select