4.2 Connection Methods
37
1
2
3
4
5
6
7
8
9
10
11
(1) Set the Wiring Method.
Wiring diagram screen
Press the F2 (WIRING) key to display the selection window.
Select a wiring method by using the cursor key.
Press the
F1
(select) key.
1P2W
Measurement of a single-phase, 2-wire line
1P3W
Measurement of a single-phase, 3-wire line
3P3W2M
Measurement of a three-phase, 3-wire line (by the two-
power-meter method)
*:
Select this method to measure three-phase power by
measuring the current at two positions only.
3P3W3M
Measurement of a three-phase, 3-wire line (by the
three-power-meter method)
3P4W
Measurement of a three-phase, 4-wire line
3P4W4I
Measurement of a three-phase, 4-wire line (used for
neutral conductor measurement)
WIRING
select