MAN0604_Issue 09_02-2013 Apex
2110M8030
4. OPERATION
CongureAlarms Conguration Menu
Caution: Alarm 2 value can be set below Alarm 1 value.
When installed to measure ammable gas it is essential that
either the Transmitter unit or control network is congured to
latch the overrange condition. If the Transmitter unit local
relays are used this should be achieved by enabling the
overrange latching function of the Transmitter unit. Depletion
of oxygen as a consequence of displacement by ammable
gas can result in the gas reading returning to zero.
Providesthemeanstocongurethepointatwhichthealarmsactivateandwhetheroverrange
latchingisrequired.Therangeofsettingsdependsonthetypeofgascartridgettedtothe
CertiedSensor.
When the Transmitter Unit’s alarm thresholds are changed, the actual cartridge parameters are
updatedtoreecttheTransmitterUnit'sconguredvalues.
The default state for Overrange latching is not latched.
When activated, overrange latching causes the Transmitter Unit to latch the A1 and A2 Alarm relays
andthe4-20mAoutputifanoverrangegasconditionisdetected.Overrangelatchingonlyeffects
alarm relay latching after an overrange condition, not at the A1 and A2 alarm thresholds. Overrange
latching only operatesin the normal Transmitter Unit active condition, not in Gas Challenge or
Gas calibrate conditions.
WARNINGS
Change cartridges using the procedure described below.
Failure to correctly follow this procedure could result in the
wrong cartridge being installed, and possibly non-detection
of events. Alternatively, extraneous alarms could be
triggered by chemicals detected but not of concern at a
particular location.
Sensor Cartridges may contain corrosive solutions.
Dispose of according to local and national regulations.
!
Configure Alarms
ok
Select alarm
action to
configure
Configure Alarms screen
Select another option?
Yes
No
ok
ok
Configuration
Menu
esc
Use up/down buttons to
choose setting from:
Alarm1 Relay
Alarm2 Relay
Overrange Latching
Set alarm value
or overrange
latching on/off
ok
Use up/down buttons