5. C300 Configuration Form Reference
5.3. CEEC300 Function Block
136
Series 8 C300 Controller User's Guide
Honeywell
R500
April 2017
Plain Text
Parameter Name
User
Configurable
Notes
Instance Count
BLKTYPCOUNT
No
Shows the number of
instances currently
loaded to the controller.
CAB Types Info tab
The CAB Types Info tab contains information about the CAB types loaded in the CEE.
The following table summarizes the parameter data you can monitor on the CAB Types
Info tab of the configuration form for the selected CEEC300 block.
Plain Text
Parameter Name
User
Configurable
Notes
CAB Supported
Version
CC3SUPRTDV
No
Provides the version
level of the CAB/C300
run-time supported by
the C300. Only CAB
types which require this
version level or lower
can be loaded to the
C300.
Enable CAB Runtime
ENABLECAB
Yes
Displays whether the
CAB in a C300 is
enabled or disabled.
For application
engineers to be able to
load CAB programs to a
C300, this parameter
must be turned “On.
This parameter is “Off
by default. You must
turn this parameter “On”
before the first CAB
load. If you want to
disable CAB in a C300
where it was previously
enabled, you must first
delete all CAB
instances and types
from the controller.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell C300 and is the answer not in the manual?

Honeywell C300 Specifications

General IconGeneral
Memory512 MB RAM, 512 MB Flash
TypeProcess Controller
Communication PortsEthernet, Serial
Power Supply24V DC
InputsAnalog and Digital
OutputsAnalog and Digital
CommunicationEthernet, Serial, HART
RedundancySupported (Hot Standby)