Series 8 C300 Controller User's Guide 
Honeywell 
10. C300 Controller Troubleshooting 
10.4. Fixing common problems 
no FTE Diagnostic messages over the sample interval of this 
diagnostic. In this case, the C300 Controller's FTE Receive Fault 
Diagnostic will indicate a spurious fault. The spurious alarm 
generated by the FTE Receive Fault Diagnostic is a relatively minor 
side effect, in the case of a network storm. A network storm is 
signaled by other alarms in the system. 
Unless you suspect that one of the causes described above exists and is 
resulting in a spurious indication, you should replace the C300 
Controller Module exhibiting this diagnostic at your earliest convenience. 
When this fault exists, network redundancy for this node no longer is 
working. See C300 Controller module and IOTA replacem ent for details. 
 
Controller does not synchronize with backup 
 
Primary controller cannot synchronize with backup. 
 
In the Monitoring tab, double-click the primary C300 icon to display its 
Parameters configuration form. Click the Redundancy tab to display it 
and check the Inhibit Sync Reason parameter for a description for the 
controller not achieving synchronization. 
 
Troubleshoot to correct condition for inhibiting sync. 
Replace redundancy cable.  Check to see if controllers synchronize. 
Controller IOLINKS may be configured for Series 8 I/O. 
IOL cables may be disconnected. 
Reconnect cables to controller IOTA. 
Replace controller module.  Refer to the section C300 Controller module  
and IOTA replacement for details. 
 
Check to see if controllers synchronize. 
Replace the IOTA.  Reinstall the original backup controller module on 
the new IOTA.  Refer to the section C300 Controller module and IOTA  
replacement for details. 
Check to see if controllers synchronize. 
Primary controller module bad.