4. C300 Controller Configuration 
4.6. Convert a redundant C300 Controller to a non-redundant controller 
Series 8 C300 Controller User's Guide 
Honeywell 
 
 
 
4.6 
Convert a redundant C300 Controller to a non-
 
redundant controller 
 
Prerequisites 
 
Control Builder is running 
 
Tree windows are open 
 
Make sure that the current primary C300 Controller is physically configured with the 
odd Device Index.  If not, enable synchronization, wait for initial-sync to complete, 
and manually command switchover. 
 
Considerations 
This procedure can be performed on-process.  All illustrations used in the procedure are 
for example purposes only. 
To convert a redundant C300 Controller to a non-redundant controller, perform the 
following steps. 
 
In the Monitor view, open the 
configuration form for the secondary 
C300 Controller block. 
Secondary C300 Block configuration form 
appears. 
Select the Redundancy tab, and click 
Disable Synchronization. 
Synchronization between primary and 
secondary C300 controllers terminates. 
 
A 'Not Synchronized' diagnostic alarm will 
be generated by both the primary & 
secondary controllers. 
Delete the C300 secondary function block 
from the Monitor view. 
C300 secondary function block is deleted 
from the Monitor view. 
Disconnect the redundancy cable from 
the primary C300 Controller. 
Remove the secondary controller 
hardware by removing the controller 
module and its IOTA. 
 
Refer to the procedure To replace a non-  
redundant controller IOTA board and 
follow the steps only to remove the 
Controller hardware is removed from the 
system.