5. C300 Configuration Form Reference
5.4. IOLINK Block
R500
April 2017
Series 8 C300 Controller User's Guide
Honeywell
143
Statistics tab
The Statistics tab contains IOLINK statistics used for maintenance and performance
monitoring of the IOLINK interface. The following table summarizes the parameter data
you can monitor on the Statistics tab of the configuration form for the selected IOLINK
block.
Plain Text
Parameter Name
User
Configurable
Notes
Reset Statistics
STATRESET
Yes
Button to initiate reset
of statistics in
Monitoring mode.
Primary Link Interface
Active Receive
Channel
PRIIFRCVCHN
No
Shows the channel that
is actively listening to
transmitted messages.
Channel A Errors
PRIIFCHNERRA
No
The number of I/O link
channel A errors
encountered locally by
the primary link
interface.
Channel A Silences
PRIIFCHNSILA
No
The number of I/O link
silences on channel A
encountered locally by
the primary link
interface.
Channel A- Edges
PRIIFCHNMNA
No
The number of I/O link
channel A missed
minus edge transitions
encountered locally by
the primary link
interface.
Channel A+ Edges
PRIIFCHNPLA
No
The number of I/O link
channel A missed and
the edge transitions
encountered locally by
the primary link
interface.