EasyManuals Logo

Honeywell C300 User Manual

Honeywell C300
285 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #146 background imageLoading...
Page #146 background image
5. C300 Configuration Form Reference
5.4. IOLINK Block
140
Series 8 C300 Controller User's Guide
Honeywell
R500
April 2017
Plain Text
Parameter Name
User
Configurable
Notes
Priority IOMs
NUMPRIORITYIOM
No
Shows the number of
IOMs configured as
Priority IOMs on the
IOLINK.
I/O Link Cable Color
IOLINKCOLOR
No
Shows the link cable
color assigned to the
IOLink number.
I/O Link Number
LINKNUM
No
Shows the link number
within the I/O Link
Interface.
I/O Link State
STATE
No
The current state of the
IOLink, (NOTLOADED,
ONLINE)
Simulation State
SIMSTATE
No
Specifies the current
state of the simulation.
I/O Link Soft Fail Errors
(Refer to the Troubleshooting section for more information.)
Duplicate IOL
Address
DUPIOLADDR
No
Indicates if a duplicate
IOLink address has
been detected.
IOL Channel A
Failure
IOLCHNFAILA
No
Indicates if Channel A
of the IOLink has failed.
IOL Channel B
Failure
IOLCHNFAILB
No
Indicates if Channel B
of the IOLink has failed.
IOL Maximum Errors
Exceeded
IOLMAXERR
No
Shows the I/O link has
exceeded the maximum
error limit.
Not Active Supervisor
NOTACTSUPV
No
Indicates that the IOL
interface daughter card
could not transition into
the active supervisor
role.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell C300 and is the answer not in the manual?

Honeywell C300 Specifications

General IconGeneral
Memory512 MB RAM, 512 MB Flash
TypeProcess Controller
Communication PortsEthernet, Serial
Power Supply24V DC
InputsAnalog and Digital
OutputsAnalog and Digital
CommunicationEthernet, Serial, HART
RedundancySupported (Hot Standby)