R500
April 2017
Series 8 C300 Controller User's Guide
Honeywell
259
10. C300 Controller Troubleshooting
10.10. Communication and system time faults during startup
Controller
Faceplate
Problem
C300 Block
Time Source
Station Alarm
Resolve
Display
BP for 2
min. TS
for 3 min.
then
IDLE
CB
icon
Red
Status
LED
Blinking
Red ->
Green
Communication on FTE
network.
No communication
through CDA
Unable to establish
connection to system
time source
Internal
CDA Comm
Lost
Connection
Not e 2
FTE
LEDs
Blinking
Green
Display
TS for 3
min. then
-> IDLE
CB
icon
Grey
Status
LED
Blinking
Red ->
Green
Communication on FTE
network
Communication
through CDA
Unable to establish
connection to system
time source
CDA
Not Using
Configured
Timesource
Not e 3
FTE
LEDs
Blinking
Green
Display
TS for 1
min.
then ->
IDLE
CB
icon
Red ->
Blue
Status
LED
Green
Communication on FTE
network
SNTP
CDA Comm
Lost
Not e 4

Table of Contents