5. C300 Configuration Form Reference
5.1. C300 Controller Block
94
Series 8 C300 Controller User's Guide
Honeywell
R500
April 2017
Plain Text
Parameter Name
User
Configurable
Notes
Redundancy Delay
(%)
RDNDELAYAVG
No
The average of
redundancy delay CPU in
percent.
Max Redundancy
Delay (%)
RDNDELAYMAX
No
Historical maximum
redundancy delay CPU
value observed since
power up or last statistics
reset.
Max Initial Sync Time
(sec)
RDNISTIMEMAX
No
Maximum initial
synchronization time, in
seconds.
Max Switchover Time
(mSec)
RDNSOTIMEMAX
No
Maximum switchover time,
in milliseconds.
OPM Freeze Ctrl
Time (msec)
Note: This parameter
is not supported in
this release.
RDNOPMFRZTIME
No
Maximum control freeze
time during an On-Process
Migration session.
Redundancy History
Time
RDNHISTTIME
No
Show time of related state.
Event
RDNHISTSTATE
No
Lists the last 16
redundancy related
activities.
Reason
RDNHISTREASON
No
Indentifies reason for
redundant history state.
Redundancy Link
Failed
RDNLINKFAILED
No
Indicates if Redundancy
link communications are
interrupted.
OPM Status
Note: This parameter
is not supported in
this release.
RDNOPMSTATUS
No
Status parameter
indicating the notifications
generated by the primary
controller during an On-
Process Migration
session.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell C300 and is the answer not in the manual?

Honeywell C300 Specifications

General IconGeneral
Memory512 MB RAM, 512 MB Flash
TypeProcess Controller
Communication PortsEthernet, Serial
Power Supply24V DC
InputsAnalog and Digital
OutputsAnalog and Digital
CommunicationEthernet, Serial, HART
RedundancySupported (Hot Standby)