EasyManuals Logo

Honeywell EXCEL 5000 User Manual

Honeywell EXCEL 5000
282 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #169 background imageLoading...
Page #169 background image
EXCEL CARE CONTROL ICONS ALPHABETIC REFERENCE
171 74-5577–33 (US)
EN2B-0184 GE51 R0518 (Europe)
EOH Operating Procedures EOH3 calculates the flow temperature setpoint with or without optimization as a
function of the room temperature setpoint TSet, the outside air temperature TOat,
the heating curve parameters curvature and slope.
Heating Curve Setpoint = HC(TSet, TOat, P16, P17)
During total cool-down (see previous section), the flow temperature setpoint can be
set to “0”.
Optimum Start can happen only if all the following conditions are true:
The "EOH / EOV Optimisation" check box of the datapoint connected to the input
TSet is checked (usually an Analog Value)
The input OptEn has one of the values, 2 or 4
The next room temperature setpoint changes from a lower to a higher value (Tset
> Tset next) with a difference of at least 1K
If you want to disable optimum start only for a few switching points, you can do it
by setting the input OptimEn
Optimum Stop can happen only if all the following conditions are true:
The "EOH / EOV Optimisation" check box of the datapoint connected to the input
TSet is checked (usually an Analog Value)
The input OptEn has one of the values, 3 or 4
The next room temperature setpoint changes from a higher to a lower value (Tset
< Tset next) with a difference of at least 1K
If you want to disable optimum stop only for a few switching points, you can do it
by setting the input OptimEN
Heating Optimization WITHOUT Room Sensor
°C
°C
P25
minimum room
temperature control
P24
mixed water temperature setpoint
night setback
room temp setpoint
time
time
room temp
preheating
occupied/
un-occupied
changeover
P20
time
room temperature setpoint
[°C]
optimum
stop
optimum
stop
optimum start
optimum
start
normal
operation
room
control
total cool-down
above frost limit
setback
operation

Table of Contents

Other manuals for Honeywell EXCEL 5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell EXCEL 5000 and is the answer not in the manual?

Honeywell EXCEL 5000 Specifications

General IconGeneral
BrandHoneywell
ModelEXCEL 5000
CategoryControl Systems
LanguageEnglish

Related product manuals