GX-Series Control Panel Installation and Setup Guide
6-113
Option 62 – Full Test
The Full Test option allows two zones to be selected and tested under full set conditions. Activating the
selected zone results in a full alarm condition, including remote signaling. Constantly active zones
(Security, 24 Hours, PA, Fire) remain active throughout the Full Test; an activation generates the
appropriate local or full alarm depending on the zone.
On selecting the Full Test option, the address and function of the first zone on the system is displayed.
Move to the required zone by pressing the A> or <B keys or by entering the zone address. Press the ent key.
An option is then given to choose a second confirm zone. If you press the A> (YES) key, select a second
required zone by pressing the ent key. If you press the <B (NO) key, the system begins the full setting
(arming) procedure. Activating the zone results in a full alarm condition. To end the full test unset (disarm)
the system.