EasyManua.ls Logo

Honeywell GX-Series - Wiring Zones

Honeywell GX-Series
208 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GX-Series Control Panel Installation and Setup Guide
2-12
Wiring Zones
The zones on GX-Series panels can be Double Balanced (default) or End of Line. Zones can be programmed
with different resistance ranges for zone status activation (see Parameter 51.46 = Parameters.Zone
Resistance). Refer to Table 2-7 (Double Balanced) or Table 2-9 (End of Line) for details of the zone
resistance and resulting conditions. The system default is Option 9, giving fault monitoring on 1k double
balanced wiring.
NOTE: The circuit debounce time (the period the zone must remain in a state to register a change in condition) is
300 milliseconds by default.
Option 01 - 1k Option 03 – 2.2k Option 05 – 4.7k Option 07 – 5.6k Option 09 - 1k Fault
Tamper S/C 0 – 800 0 – 1800 0 – 3700 0 -1400 0 - 800
Low Res 800 – 900 1800 – 2000 3700 – 4200 1400 – 2800 800 - 900
Normal 900 – 1200 2000 – 2500 4200 – 5500 2800 – 8400 900 -1200
High Res 1200 – 1300 2500 – 2700 5500 – 6500 8400 – 9800 1200 - 1300
Open 1300 – 12000 2700 – 12000 6500 – 19000 9800 – 12600 1300 - 3500
Fault - - - - 3500 - 4500
Masked 12000 – 19000 12000 – 15000 19000 – 22000 12600 – 22000 4500 - 19000
Tamper O/C 19000 – infinity 15000 – infinity 22000 – infinity 22000 – infinity 19000 - infinity
Table 2-6. Double Balanced Zone Resistance and Conditions
Option 09 - 1k Fault Double-balanced (default)
The wiring in Figure 2-12 should be used if the detector uses combined fault and mask signaling. A mask
condition is generated if an alarm and fault are signaled at the same time. Alternatively, if the detector has
separate fault and mask indications then the wiring in Figure 2-13 should be used.
Zone
1k
328 ft (100 m)
Tamper N/C
1k
Alarm N/C Fault N/C
3k
GX-012-V1
Figure 2-12. Option 09 - Double balanced 1k Fault Monitoring Wiring
Zone
Tamper N/C
1k
Alarm N/C
Fault N/C
3k 12k
Anti-mask N/C
GX-013-V2
328 ft (100 m)
Figure 2-13. Option 09 - Double balanced 1k Fault/Mask Monitoring Wiring
NOTES: For UL Installations, use 1K Ohm single EOL resistor configurations; the maximum loop impedance is 100 Ohms.
N/C = Normally Closed.

Table of Contents

Related product manuals