Environmental specifications-system components support matrixEnvironmental specifications-system components support matrix
EnvironmentalEnvironmental
specificationspecification
Support statusSupport status
BaseBase
systemsystem
FansFans SFF drivesSFF drives SATA M.2SATA M.2
drivesdrives
NVME M.2NVME M.2
drivesdrives
PCIe I/OPCIe I/O
cardscards
PXIe I/OPXIe I/O
cardscards
Standard
Operating
Support
Yes Yes (with
redundancy)
Yes Yes Yes Yes Yes (up to 38
W)
Extended
Ambient 40°C
Operating
Support
(ASHRAE Class
A3 Compliant)
Yes Yes (with
redundancy)
Yes Yes Yes Yes Yes (up to 38
W)
Extended
Ambient 45°C
Operating
Support
(ASHRAE Class
A4 Compliant)
Yes Yes (with
redundancy)
Yes (less than 8
W)
Yes Yes Yes Yes (up to 38
W)
Extended
Edgeline 0°C to
55°C Operating
Support
Yes Yes (with
redundancy)
No Yes No Yes Yes (up to 38
W)
Maximum altitude is 2,000 m (800 mbar) (at 25 °C ambient temperature)
Upon fan failure, the servers in the system might have reduced performance.
M.2 drive might exceed its spec by 2°C to 3°C and have slight throttling.
Near 55°C inlet ambient temperature, when the CPU is stressed at 100%, the HPE m510 -16c server might have reduced performance.
The PCI card must have inlet spec rated at 65°C or higher, and an air speed of 375 ft/min.
1