HPE 800W Flex Slot -48VDC Hot-plug Low Halogen Power Supply
Specification Value
Input requirements
Rated input voltage
-40 VDC to -72 VDC
-48 VDC nominal input
Rated input current
221 A at -40 VDC input
182 A at -48 VDC input, nominal input
120 A at -72 VDC input
Rated input power (W)
874 W at -40 VDC input
865 W at -48 VDC input, nominal input
854 W at -72 VDC input
Rated input power (BTUs per hour)
2983 at -40 VDC input
2951 at -48 VDC input, nominal input
2912 at -72 VDC input
Power supply output
Rated steady-state power (W) 800 W at -40 VDC to -72 VDC
Maximum peak power (W) 800 W at -40 VDC to -72 VDC
Maximum peak power
800 W at -40 VDC to -72 VDC input
WARNING: To reduce the risk of electric shock or energy hazards:
This equipment must be installed by trained service personnel.
Connect the equipment to a reliably grounded secondary circuit source. A secondary circuit has no direct
connection to a primary circuit and derives its power from a transformer, converter, or equivalent isolation
device.
The branch circuit overcurrent protection must be rated 27 A.