Item Method Expected Result Troubleshooting
ECC800-Pro RUN
indicator (green)
Check the
RUN indicator
on the
ECC800-Pro
main control
module.
The RUN indicator
blinks slowly.
If the RUN
indicator blinks
fast, check
whether the
communications
cable is properly
connected
between the
ECC800-Pro and
the host.
If the RUN
indicator is
o,
rectify any input
power grid fault.
Ambient
temperature
detection
- The ambient
temperature of the
smart module
should be lower
than 45°C.
Find the cause of an
abnormal
temperature.
Indicators on the
iBOX (CIM) and
iBAT (BIM)
Visual
inspection
The RUN
indicator blinks
at long intervals.
The ALM
indicator is o.
If the RUN
indicator blinks
at short intervals,
check whether
the
communications
cable is loose or
disconnected. If
so, reconnect the
cable. If not,
replace the cable.
If the ALM
indicator is
steady on, clear
the alarm by
referring to the
iBattery user
manual.
FusionModule2000 Smart Modular Data Center
Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance
Issue 01 (2020-12-25) Copyright © Huawei Technologies Co., Ltd. 27

Table of Contents

Other manuals for Huawei FusionModule2000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule2000 and is the answer not in the manual?

Huawei FusionModule2000 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule2000
CategoryStorage
LanguageEnglish

Related product manuals