Figure 5-63 Connecting a conversion cable to a water detector
Step 2 Replace a water detection cable.
1. Remove the faulty water detection cable from the port.
2. Install a new water detection cable.
Figure 5-64 Connecting a new water detection cable
(1) Conversion cable end B, connecting to the
water detection cable
(2) Water detection rope end A, connecting to
the conversion cable
NO TE
The water detection cable and conversion cable are interconnected through the male and
female connectors.
Step 3 Check whether the new water detector works properly. Connect the network cable
between the water detector and ECC, immerse the water detection cable in water,
and check whether an alarm is generated. If an alarm is generated, the
replacement is complete.
Step 4 Wipe dry the water detection cable. The alarm automatically disappears.
----End
5.4.13 Replacing an Alarm Beacon
Impact on the System
No sound or
ash can be generated by the alarm.
Preparations
Tools: Phillips screwdriver, step ladder
Material: alarm beacon
FusionModule2000 Smart Modular Data Center
Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement
Issue 01 (2020-12-25) Copyright © Huawei Technologies Co., Ltd. 113

Table of Contents

Other manuals for Huawei FusionModule2000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule2000 and is the answer not in the manual?

Huawei FusionModule2000 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule2000
CategoryStorage
LanguageEnglish

Related product manuals