Figure 5-63 Connecting a conversion cable to a water detector
Step 2 Replace a water detection cable.
1. Remove the faulty water detection cable from the port.
2. Install a new water detection cable.
Figure 5-64 Connecting a new water detection cable
(1) Conversion cable end B, connecting to the
water detection cable
(2) Water detection rope end A, connecting to
the conversion cable
The water detection cable and conversion cable are interconnected through the male and
female connectors.
Step 3 Check whether the new water detector works properly. Connect the network cable
between the water detector and ECC, immerse the water detection cable in water,
and check whether an alarm is generated. If an alarm is generated, the
replacement is complete.
Step 4 Wipe dry the water detection cable. The alarm automatically disappears.
----End
5.4.13 Replacing an Alarm Beacon
Impact on the System
No sound or
ash can be generated by the alarm.
Preparations
● Tools: Phillips screwdriver, step ladder
● Material: alarm beacon
FusionModule2000 Smart Modular Data Center
Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement
Issue 01 (2020-12-25) Copyright © Huawei Technologies Co., Ltd. 113