Locati
on
Display Name Addr
ess
DIP Switch No.
1 2 3 4 5 6
Hot aisle 2
temp/humid
22 OFF ON ON OFF ON OFF
Hot aisle 3
temp/humid
23 ON ON ON OFF ON OFF
Hot aisle 4
temp/humid
24 OFF OFF OFF ON ON OFF
Hot aisle 5
temp/humid
25 ON OFF OFF ON ON OFF
Step 7 Install the air lter and close the rear door.
----End
5.4.12 Replacing a Water Sensor
The water sensor can be installed in various scenarios. This section describes the
general method for replacing a water sensor.
Context
Prepare a water sensor or water detection cable of the same model.
A water sensor consists of a water detection cable, water detector, and conversion
cable. The water detection cable is laid out on the
oor, connected to the water
detector placed near the collector by the conversion cable.
FusionModule2000 Smart Modular Data Center
Maintenance Guide (Fusion Module Actuator) 5 Parts Replacement
Issue 01 (2020-12-25) Copyright © Huawei Technologies Co., Ltd. 111

Table of Contents

Other manuals for Huawei FusionModule2000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule2000 and is the answer not in the manual?

Huawei FusionModule2000 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule2000
CategoryStorage
LanguageEnglish

Related product manuals