Item Method Expected Result Troubleshooting
Fire control
linkage function
Generate
smoke
under a
smoke
detector or
multi-
functional
sensor. (If
real smoke
is not
allowed,
press the
TEST button
on the
sensor.)
A smoke alarm
is displayed on
the active
alarm page of
the WebUI.
The skylight is
opened.
The alarm
beacon
produces
audible and
visual alarms.
Check whether the
smoke detector or
multi-functional
sensor is faulty.
Check whether the
skylight system is
normal.
If the alarm beacon
produces audible
and visual alarms,
check whether the
alarm beacon is
faulty and whether
the cable
connection is
proper.
Connection of
iBAT (BIM)
Check
whether the
iBAT (BIM)
is attached
rmly and
whether all
cables are
securely
connected.
The iBAT (BIM)
is attached
rmly.
All iBAT (BIM)
cables are
securely
connected.
No iBAT (BIM)
cable
deteriorates
and the
insulation layer
does not crack.
Secure the iBAT
(BIM) again.
Check that all iBAT
(BIM) cables are
securely connected.
Replace the faulty
cable.
FusionModule2000 Smart Modular Data Center
Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance
Issue 01 (2020-12-25) Copyright © Huawei Technologies Co., Ltd. 31

Table of Contents

Other manuals for Huawei FusionModule2000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule2000 and is the answer not in the manual?

Huawei FusionModule2000 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule2000
CategoryStorage
LanguageEnglish

Related product manuals