Item Method Expected Result Troubleshooting
Cleanliness of the
smart cooling
product
Visual inspection The white paper
that you use to
wipe the cabinet
panel is clean.
If the white paper
turns black, clean
the smart cooling
product cabinet.
Outdoor fan Visual inspection The fan runs
properly
without
abnormal noise
or vibration,
and the blades
rotate properly.
Cables are not
damaged or
aged.
Power o the
outdoor unit
and replace
the fan
component.
Power
o the
outdoor unit
and replace
cables.
Table 3-10 Semiannual maintenance for the management system
Item Method Expected Result Troubleshooting
Availability
of the smart
ETH gateway
On the ECC800-
Pro WebUI,
choose
Monitoring >
System > Smart
ETH Gateway
Group > Smart
ETH Gateway.
On the Running
Info page, view
the
communication
status, PoE port
connection, and
power supply
status.
The connection
status and power
supply status of the
PoE port on the
smart ETH gateway
can be queried on
the ECC800-Pro
WebUI.
If the display is
abnormal, check
whether the
communications
cable is loose or
disconnected. If so,
reconnect the cable.
If not, replace the
smart ETH gateway.
FusionModule2000 Smart Modular Data Center
Maintenance Guide (Fusion Module Actuator) 3 Routine Maintenance
Issue 01 (2020-12-25) Copyright © Huawei Technologies Co., Ltd. 38

Table of Contents

Other manuals for Huawei FusionModule2000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule2000 and is the answer not in the manual?

Huawei FusionModule2000 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule2000
CategoryStorage
LanguageEnglish

Related product manuals