● Maximum capacity: In single-system scenarios, a maximum of six battery modules can
be connected. In parallel-system scenarios, a maximum of three power modules can be
connected. Each power module can connect to a maximum of three battery modules.
● In parallel-system scenarios, three routes of single-phase output can be combined but
they cannot be used as three-phase output.
● In parallel-system scenarios, it is recommended that the number of battery modules on
the master and slave products be the same.
● In parallel-system scenarios, if the number of battery modules in the master product is
dierent from that in the slave product (not recommended), for example, two power
modules and ve battery modules, the power/capacity of battery modules is 9 kW/25
kWh.
● In parallel-system scenarios, if the number of battery modules in the master product is
dierent from that in the slave product (not recommended), the products with larger
capacity may fail to fully discharge in heavy load scenarios.
● One power module and one battery module: If the product supplies power separately,
the load power cannot exceed 2.5 kW. If the load power exceeds 2.5 kW, the product
shuts down for 10 seconds and then restarts, which repeats for three times. The product
runs with a power limit of 2.8 kW for 1 hour and then stops working.
Table 4-5 Recommended battery
conguration
Scenario Number of
Power
Modules
Number of
Battery
Modules
Maximum
Output
Power
Capacity
Single system 1 1 2.5 kW 5 kWh
2 5 kW 10 kWh
3 5 kW 15 kWh
Single system
(capacity
expansion
scenario)
4 5 kW 20 kWh
5 5 kW 25 kWh
6 5 kW 30 kWh
Parallel
system
2 2 5 kW 10 kWh
4 9 kW 20 kWh
6 9 kW 30 kWh
3 3 7.5 kW 15 kWh
6 13.5 kW 30 kWh
9 13.5 kW 45 kWh
iSitePower-M (MAP05A1, MAB05B1)
User Manual 4 Product Description
Issue 06 (2023-04-24) Copyright © Huawei Digital Power Technologies Co., Ltd. 36