to the value of End-of-Discharge SOC for Lithium Batteries(%), the loads
power o.
3. After the ESS discharge ends, the PV system charges the ESSs. When the value
of Available SOC for Lithium Batteries(%) is reached, the ESSs resume
power supply to loads.
Table 6-1 Lithium battery parameters
End-of-Discharge SOC for
Lithium Batteries(%)
Available SOC for Lithium Batteries(%)
Value Range Default Value Value Range Default Value
5–15 5 20–95 20
● Lithium battery SOC: lithium battery real-time capacity percentage.
● End-of-Discharge SOC for Lithium Batteries(%): In any mode, the ESSs discharge to
the value of End-of-Discharge SOC for Lithium Batteries(%), protecting the batteries.
● Available SOC for Lithium Batteries(%): When the ESSs have only PV input (no AC
input), the ESSs discharge to the value of End-of-Discharge SOC for Lithium
Batteries(%). The PV system charges the ESSs until the value of Available SOC for
Lithium Batteries(%) is reached. Then the ESSs supply power to loads. This prevents
unstable power supply when the irradiance is low.
Parameters Settings
Figure 6-1 Setting basic parameters
iSitePower-M (MAP05A1, MAB05B1)
User Manual 6 Application Scenarios
Issue 06 (2023-04-24) Copyright © Huawei Digital Power Technologies Co., Ltd. 49