Possible Cause Solution
a0
14
Com
p
short
perio
d
MAJ
OR
- The
alarm
is
genera
ted.
1. The comp starts
and stops
frequently,
aected by other
alarms.
2. The load is low,
which leads to
the comp
starting and
stopping
frequently.
1. Clear other
alarms.
2. Please consult
Huawei
technical
support.
a0
15
Com
p
excee
d
runti
me
Warn
ing
30000
hours
The
alarm
is
genera
ted.
The accumulated
runtime of the
compressor exceeds
the alarm thres.
Maintain or
replace the comp.
Tap Maint >
Performance
Maint to clear the
accumulated
runtime.
a0
18
Indo
or
fan 1
excee
d
runti
me
Indo
or
fan 2
excee
d
runti
me
Warn
ing
40000
hours
The
alarm
is
genera
ted.
The accumulated
runtime of the fan
exceeds the alarm
thres.
Maintain or
replace the indoor
fan. Tap Maint >
Performance
Maint to clear the
accumulated
runtime.
a0
22
Humi
dier
excee
d
runti
me
Warn
ing
3000
hours
The
alarm
is
genera
ted.
The accumulated
runtime of the
humidier exceeds
the alarm thres.
1. Maintain or
replace the
humidier.
2. Tap Maint >
Performance
Maint to clear
the
humidier
total runtime.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width) 6 System Operation and Maintenance
Issue 17 (2020-10-22) Copyright © Huawei Technologies Co., Ltd. 165