T/H Curve
Indicates curves for recent (time optional) temperature and humidity changes.
Teamwork
Sets and checks teamwork control information based on the requirements of
the smart cooling product.
Running
Checks the component status, system parameters, and the name, control and
operating status, and other related information of the components in the
current smart cooling product system.
Alarms
Checks the active and historical alarms of the smart cooling product, and
deletes the historical alarms.
Settings
Sets the involved parameters for the operation of the smart cooling product.
Maint
Checks or deletes the logs or component total runtime/run factor, manually
diagnoses each component, calibrates the sensor and touch screen, exports
data, and upgrades the system.
About
Checks the model, manufacturer, monitoring version, detail version
information, and electronic label of the ACC.
4.5 Power-On Commissioning
4.5.1 Quick Settings
Prerequisites
After the system is powered on, the LCD is started, and the progress bar in the
startup screen is full:
For initial power-on, the system enters the quick setting screen. Set the
parameters by following the instructions in this section.
For non-initial power-on, the LCD automatically enters the home screen as
shown in Figure 4-3.
Procedure
Step 1 Set the language and tap Next, as shown by (1) in Figure 4-5.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width) 4 ACC Introduction
Issue 17 (2020-10-22) Copyright © Huawei Technologies Co., Ltd. 89