EasyManua.ls Logo

Huawei NetCol5000-A035 - Setting Communications Parameters (IP Address Settings); Setting Communications Parameters (Modbus Settings)

Huawei NetCol5000-A035
244 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.5.2.4 Setting Communications Parameters (IP Address Settings)
Context
When the smart cooling product monitoring system connects to the ECC800,
you do not manually set the IP address and skip the operations in this section.
To set communications parameters, log in as the Admin, or Engineer user.
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > IP Settings. Figure 4-9
is displayed.
Figure 4-9 Setting the IP address, subnet mask, and gateway address
Step 2 Set the parameters by referring to Table 4-4.
Table 4-4 IP address settings
Parameter
Setting Method
IP address Set according to the actual plan
Subnet mask Set according to the actual plan
Gateway Set according to the actual plan
----End
4.5.2.5 Setting Communications Parameters (ModBus Settings)
Context
When the smart cooling product monitoring system connects to the ECC800,
you do not manually set the Modbus and skip the operations in this section.
To set communications parameters, log in as the Admin or Engineer user.
If Connection mode is set to Server, one smart cooling product can be
accessed by a maximum of two element management system (EMS) clients
at the same time. If Connection mode is set to Client, a smart cooling
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width) 4 ACC Introduction
Issue 17 (2020-10-22) Copyright © Huawei Technologies Co., Ltd. 95

Table of Contents

Other manuals for Huawei NetCol5000-A035

Related product manuals