Name Specications
Power requirements Earth leakage circuit breakers are not recommended for
mains. If earth leakage circuit breakers are required by
the customer or according to local regulations, use the
residual current circuit breaker (RCCB) that is not
sensitive to the single-phase DC pulse and transient
current pulse.
Note: If the requirements are not met, contact Huawei technical support for an
optimized plan.
Water Quality Requirements
NO TICE
If the inlet water contains large granules, install a water ltering device at the
inlet port to prevent pipe blockage.
Table 2-7 describes NetCol5000-A water quality requirements.
Table 2-7 Water quality requirements
Name
Specications Unit
Hydrogenion 7–8.5 pH
Conductivity rate at 20°C
20
)
a
300–1250 μS/cm
a: When σ
20
is less than 300 μS/cm, the rst vapor exhausting duration of the
humidier is long; when σ
20
greater than 1250 μS/cm, the humidier service life
is
aected.
2.4 Technical Specications
Table 2-8 General Parameters
Item
NetCol5000-A035 NetCol5000-A025
Cooling Mode Air cooled Air cooled
Refrigerant R410A R410A
Cooling capacity
a
35 kW 25 kW
Air supply mode Horizontal air supply Horizontal air supply
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width) 2 Product Description
Issue 17 (2020-10-22) Copyright © Huawei Technologies Co., Ltd. 21