Item NetCol5000-A035 NetCol5000-A025
Airow
6800 m
3
/h 4600 m
3
/h
Air lter G4 lter G4 lter
Dimensions (H x D x
W)
b
2000 mm x 600 mm x
1100 mm
2000 mm x 600 mm x
1100 mm
a: Indoor dry-bulb temperature: 37.8°C. Wet-bulb temperature: 20.8°C.
Condensing temperature: 45°C.
b: Frames can be used to expand the depth to 1200 mm, while top supports can
be used to top frame to 2200 mm.
● When the total load of servers, relative to a single smart cooling product, is less
than 10 kW, smart cooling products that have heating and humidication
functions or partial heating and humidication functions are recommended.
● The condensate pump is mandatory for scenarios where pipes are routed from
the top or if it is required by the customer.
Table 2-9 Optional Parameters of NetCol5000-A035
Item
NetCol5000-
A035H512D2
E120E1
NetCol5000-
A035H512D2
E120E0
NetCol5000-
A035H512D2
0020E1
NetCol5000-
A035H512D2
0020E0
Max Current 32 A 32 A 26 A 26 A
Condensate
pump
Yes No Yes No
Reheat Yes Yes No No
Humidify Yes Yes No No
Reheating
capacity
6.0 kW 6.0 kW N/A N/A
Humidifying
capacity
3.0 kg/h 3.0 kg/h N/A N/A
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width) 2 Product Description
Issue 17 (2020-10-22) Copyright © Huawei Technologies Co., Ltd. 22