EC fan
The indoor curves EC retroverted centrifugal fan from a high-end German
brand conserves 40% more energy than common fans and features
redundancy design, high reliability, and long service life.
Evaporator
The highly
ecient nned-tube evaporator is made of threaded copper tubes
and a hydrogen-plated layer and adopts the computational uid dynamics
(CFD) to improve heat exchange eciency.
Air lter
The G4 air lter meets requirements for equipment room cleanness.
Electric heater
The positive temperature
coecient (PTC) heater automatically adjusts
heating capacity and provides multiple protection mechanisms to ensure
operating security and reliability. The electric heater features quick start, large
heating capacity, and even heating.
Electrode
humidier
The electrode humidier provides stepless adjustment of humidication
capacity and precise control of humidity in the equipment room.
Condensate pump
The condensate pump is made of thermostable materials which ensure that
the condensate water and hot water from the
humidier are exhausted
eciently. The pump lift is 3.5 m. Two oats are used to improve reliability.
2.2.2 Outdoor Unit
For details about the outdoor unit, see the
NetCol500 Variable-frequency Drive
Outdoor Unit User Manual
.
2.2.3 Controller
LCD
The 7-inch true color-sensitive LCD with thin
lm transistor (TFT) oers a user-
friendly interface for you to perform query, settings, monitoring, and maintenance.
Figure 2-4 shows an LCD.