The wiring terminals must stay in good contact with the oats. Otherwise, the
condensate pump cannot start properly.
Figure 3-13 Removing the transport fasteners from the oats and connecting the
wiring terminals
● The wiring terminal to the low oat has been factory installed.
● Put away the removed rubber
xing objects. If the container is to be transported again,
remove the wiring terminal from the high oat and reinstall them.
----End
3.4.2 Removing the Transport Fasteners from the Compressor
Context
When removing transport fasteners, do not remove the fuel return solenoid valve.
Otherwise, the solenoid valve might be burnt due to improper reinstallation.
Procedure
Step 1 Loosen the three bolts on the compressor using a 13# solid wrench, as shown in
Figure 3-14.
Do not directly take the bolts out.
Step 2 Remove the transport fasteners.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width) 3 Installation Guide
Issue 17 (2020-10-22) Copyright © Huawei Technologies Co., Ltd. 41