Huawei NetCol5000-A035 - 6.4 Troubleshooting

Huawei NetCol5000-A035
244 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Al
ar
m
ID
Alar
m
Alar
m
Seve
rity
Defau
lt
Value
Impac
t
Possible Cause Solution
a0
93
High
humi
dity
Warn
ing
85% The
alarm
is
genera
ted.
1. The load is low.
2. The T/H sensors
are located in
inappropriate
positions.
3. The ambient
humidity is high.
4. The high
humidity alarm
thres is
inappropriate.
5. The humidity
displayed is
dierent from
the actual
humidity.
1. Please consult
Huawei
technical
support.
2. Adjust the
positions of the
T/H sensors.
3. Check the
ambient
humidity.
4. Adjust the high
humidity alarm
thres.
5. Calibrate or
replace the
abnormal T/H
sensors.
a0
94
Low
humi
dity
Warn
ing
10% The
alarm
is
genera
ted.
1. The T/H sensors
are located in
inappropriate
positions.
2. The ambient
humidity is low.
3. The low
humidity alarm
thres is
inappropriate.
4. The humidity
displayed is
dierent from
the actual
humidity.
1. Adjust the
positions of the
T/H sensors.
2. Check the
ambient
humidity.
3. Adjust the low
humidity alarm
thres.
4. Calibrate or
replace the
abnormal T/H
sensors.
a0
95
Com
p
drive
short
perio
d
Critic
al
N/A The
alarm
is
genera
ted.
The comp driver is
faulty for multiple
times, or the faulty
lasts for a long
time.
Maintain or
replace the comp
driver.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width) 6 System Operation and Maintenance
Issue 17 (2020-10-22) Copyright © Huawei Technologies Co., Ltd. 188