Al
ar
m
ID
Alar
m
Alar
m
Seve
rity
Defau
lt
Value
Impac
t
Possible Cause Solution
a1
10
Cold
aisle
1
T/H
brd
com
m
faile
d
Cold
aisle
2
T/H
brd
com
m
faile
d
Cold
aisle
3
T/H
brd
com
m
faile
d
Majo
r
N/A The
alarm
is
genera
ted.
1. The cables to the
T/H sensor are
loose or
damaged.
2. The DIP switch
of the T/H
sensor is set
incorrectly.
3. The T/H sensor
is faulty.
4. The
communication
port of the
control board is
faulty.
1. Check the
cables to the
T/H sensor.
2. Set the DIP
switch of the
T/H sensor
correctly.
3. Maintain or
replace the T/H
sensor.
4. Maintain or
replace the
control board.
a1
11
Hot-
aisle
1
temp
invali
d
Hot-
aisle
2
temp
invali
d
Hot-
aisle
3
temp
invali
d
Majo
r
N/A The
alarm
is
genera
ted.
1. Dirt or water
exists around the
T/H sensor,
which leads to a
detection fault.
2. The T/H sensor
is faulty.
1. Remove dirt or
water from the
T/H sensor.
2. Maintain or
replace the T/H
sensor.