Table 3-10 Cable specications
Name Specications Quantity Remarks
Indoor unit
power
cable
Four-core cable
a
: electrical power
cable-600 V/1000 V-ZA-RVV-6 mm
2
-46
A
1 PCS (The
length is
determine
d in
presale
survey.)
Optional
L1, L2, and L3 terminals: common
terminal-single cord end terminal-6
mm
2
-0.02 m-30 A-inserted depth 12
mm
6 PCS Mandatory
PE terminals: naked crimping terminal-
OT-6 mm
2
-M6-50 A-tin plated-12 AWG
to 10 AWG
2 PCS Mandatory
Outdoor
unit power
cable
For detail cable specications, see the
outdoor unit user manual.
1 PCS Optional
Voltage
jumper
Six voltage jumpers are available in the
tting bag. Select one for use.
1 PCS Mandatory
Outdoor
unit on/o
signal
cable
For details about the cable
specications, see the outdoor unit user
manual.
1 PCS Optional
Water
sensor
signal
cable
Power cable-5m-22AWG-(2 x T0.5
2
)-(2
x 22UL1007)-(2 x T0.5
2
)
1 PCS Mandatory
Teamwork
networkin
g cable
It also can be used for host monitoring. 1 PCS
(10m)
Mandatory
Humidity
and
temperatu
re sensor
and its
cable
N/A Max 6 PCS Optional
a: If you use a ve-core cable, do not install the neutral wire (blue). Instead, cut
o it and properly wrap PVC insulation tape around the cutting place. Purchase
indoor unit power cables with qualied diameters (16.8–18 mm). Otherwise, the
power cables will fail to be routed through the clip.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width) 3 Installation Guide
Issue 17 (2020-10-22) Copyright © Huawei Technologies Co., Ltd. 34