Step 2 Install the pipe adapter and seal the adapter using sealant, as shown by 2 in
Figure 3-29.
Step 3 Wrap the pipe with heat insulation cotton and install the pipe and hoop, as shown
by 3 in Figure 3-29.
----End
Example
A
humidier water inlet pipe and a condensate pump drainpipe are routed from
the bottom or top. You can route the pipes based on site requirements.
CA UTION
When routing pipes from the top, do not route the pipes over servers. If
unavoidable, take protective measures to protect the servers from being
aected
by pipe leakage.
NO TICE
Do not remove the humidier water inlet pipe to prevent sealing fault between
water inlet pipe and the humidier cylinder.
The humidier water inlet pipe is a hose installed under the humidier. When
connecting the hose, straighten the hose and secure it with cable ties.
The top and bottom pipe routing methods are the same with that of self-
drainpipes. Figure 3-30 and Figure 3-31 respectively show top and bottom pipe
routing.