Check Item Expected Result Actual Result
Electrode
humidier
The water inlet pipes and drainpipes are
securely connected without leakage.
□Passed.
□Failed.
The electrode humidier is securely
connected to its base.
□Passed.
□Failed.
Compressor The sheet metal for transporting the
compressor is removed.
□Passed.
□Failed.
The valve rod of the compressor fuel return
solenoid valve is inserted in the solenoid
valve coil bottom.
□Passed.
□Failed.
The bolts on the compressor are tightened. □Passed.
□Failed.
Condensate
pump
The water inlet pipes and drainpipes are
securely connected without leakage.
□Passed.
□Failed.
The condensate pump is securely connected
to its base.
□Passed.
□Failed.
Water level
detection switch
The detection switch bands are removed. □Passed.
□Failed.
The detection switch terminals are
connected and the cables are xed.
□Passed.
□Failed.
The water level detection switch is securely
installed.
□Passed.
□Failed.
The detection switch for the water level
detection switch can move smoothly.
□Passed.
□Failed.
Air lter The air lter is correctly installed according
to the air ow direction on the frame.
□Passed.
□Failed.
Dierential
pressure switch
The cable ties on the dierential pressure
tubes are secured.
□Passed.
□Failed.
There is no foreign matter in the dierential
pressure tubes. The dierential pressure
tubes are not seriously bent.
□Passed.
□Failed.
Table 3-19 Pipeline checklist
Expected Result
Actual Result
Ports are connected correctly. The pipelines have oil trap,
inverted traps, gradients (of refrigerant pipes), and bases.
□Passed.
□Failed.
The hose clamp and cable ties of the condensate water pipes
are secured.
□Passed.
□Failed.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width) 3 Installation Guide