● Direct sunlight: In high-temperature areas, avoid exposing the outdoor unit to
direct sunlight.
● Wind and sand: Prevent sand from entering the condenser in deserts and
windy and sandy areas.
Space Requirements
The NetCol500 outdoor units can be installed horizontally, vertically, or compactly.
Figure 4-5, Figure 4-6, and Figure 4-7 show the horizontal and vertical
installation. Figure 4-8 and Figure 4-9 show the compact outdoor unit installation
requirements.
● The shaded parts in the gures are obstacles. The distances marked are the minimum
distances required between an outdoor unit and obstacles.
● The horizontal installation and vertical installation take NetCol500-A080 and
NetCol500-A060 as examples.
Horizontal and vertical installation scenarios
Figure 4-5 Space requirements for horizontal installation (unit: mm)
Figure 4-6 Space requirements for vertical installation (unit: mm)
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual 4 Installation