IDEC SmartRelay functions
187
IDEC SmartRelay Manual
The thermocouples available have the following technical
data: -30 to +70°C, 0 to 10 VDC.
See also Chapter 4.3.6.
Configuration (example):
B3 1+
On =+00015
Off =+00005
Protection mode
On threshold
Off threshold
Press
B3 2
A =00.10
B =-00030
p=0
Gain
Offset
Decimals in the message text
(if used)
View in parameter assignment mode (example):
B3 1
On =+00015
Off =+00005
On threshold
Off threshold
Application Internal mapping
-30 to +70 °C = 0 to 10 V DC 0 to 1000
0 °C 300
Offset = -30
Range of values:
-30 to +70 °C = 100
1000
Gain = 100/1000 = 0.1
On threshold = 15 °C Threshold = 15
Off threshold = 5 °C Threshold = 5