EasyManuals Logo

IDEC SmartRelay FL1D Series User Manual

IDEC SmartRelay FL1D Series
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #210 background imageLoading...
Page #210 background image
IDEC SmartRelay functions
IDEC SmartRelay Manual 200
Restriction
A maximum of 10 message text functions are available.
Functional description
With the 0 to 1 transition of the signal at input En and when
the system is in RUN, the message text you have configured
(process variable, text, time-of-day, date) is output to the dis
-
play.
Acknowledgment disabled (Quit = Off):
The message text is hidden when the status of the signal at
input En changes from 1 to 0.
Acknowledgment enabled (Quit = On):
When the status of the signal at input En changes from 1 to
0, the message text is output until it is acknowledged with
OK. When En = 1, you can not acknowledge the message
text.
When multiple message text functions are triggered with
En=1, the message text that has the highest priority is shown
(0 = lowest, 30 = highest). This also means, that a newly ac
-
tivated message text is shown only if its priority is higher than
that of previously activated message texts.
After a message text is disabled or acknowledged, the func-
tion automatically shows the previously active message text
that takes the highest priority.
You can change the view and the message texts by pressing
the keys
and .
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDEC SmartRelay FL1D Series and is the answer not in the manual?

IDEC SmartRelay FL1D Series Specifications

General IconGeneral
BrandIDEC
ModelSmartRelay FL1D Series
CategoryControl Unit
LanguageEnglish

Related product manuals