Programming manual
Programming timers 51
Chapter
8
Programming timers
Each timer can be programmed to manage:
• two scheduled activation times (“ON”) for each day of the week.
• two scheduled deactivation times (“OFF”) for each day of the week.
•Up to 15 exceptions
• the assigned partitions of the codes and keypads that have access to the programming
process of the timers via the user menu
A timer can be associated with:
•a Partition - if a timer is associated with a partition on which automatic-arming operations
are enabled (refer to paragraph 5-5 Activations in the User's Manual), the partition will arm
when the timer activates and disarm when the timer deactivates.
• Code - if a code is associated with a timer, it will be enabled to operate the system when
the timer switches ON, and disabled when the timer switches OFF.
•a Key - if the timer is enabled, the key will be authorized to operate on the system only
when the timer is active (ON).
Note
The timers must be enabled/disabled by the user (refer to paragraph 5-5 Activations in the User's
manual).
On exiting the programming session all the timers will be re-enabled automatically, therefore, if any of
the timers were previously disabled then it will be necessary to reinstate their previous status.
Via softwareClick on the Timer button on the menu on the left, the section on the right will provide a list
of all the available timers and their parameters. Selecting one of the options will allow you to
configure the parameters of the single timer by clicking on the button.
The software program allows you to configure up to 15 exceptions for each timer. Each
exception allows you to define an interval period (of even one day) within which you can set
an activation time and a deactivation time valid for all the days of the interval. The system
does not accept intervals which go over the end of the year. Therefore, it is impossible to
program an interval such as 12th December to 5th January. In such situations, you must
program 2 “timer exceptions”, one from 12th to 31st December and the other from the 1st to
5th January, both with the same On and Off settings.
The exceptions have priority over the days of the week. For example, If a “timer exception”,
let's say 1st May, falls on a Tuesday the settings programmed for 1st May will be applied.
Via keypad
Type-in Code
(Installer PIN),
PROGRAMMING Timers
This section allows you to program the various options of the selected timer.
Note
The exceptions cannot be programmed via keypad.