88 Compliance with rules in force
Anti-intrusion control panels
“Failed to arm” and “Forced arming” events must be saved to the Events log.
The programmed “LowBattery delay” must not be programmed at more than 5 minutes.
19-2
EN50131-3 and EN50131-6 grade 3
Compliance with the EN50131-3 and EN50136-3 grade 3 standards is
guaranteed by adding to the requirements indicated in the paragraph 19-1
EN50131, Grade 2 the following.
OPTIONS
Enable the “50131 grade 3 compatibility” control panel option (Table 4-6: Parameters for
compliance).
ANTI-MASKING
DETECTORS
If the installation uses detectors with an anti-masking function, each anti-masking signal
must be managed as follows:
Prepare an input terminal for the anti-masking signal connection.
“Description” parameter: assign an explanatory description to the signal
Enable “Zone fault” option
Enable the “Do not arm if zones are not ready” (Table 4-3: Control panel options)
ATS4
Use an ATS4 notification appliance:
protocol: SIA-IP with encryption
interface: LAN (integrated on the motherboard) or PrimeLAN